Skip to content

Cooling Mode not available #746

Open

Description

@bekra00

I need in HomeAssistant the cooling mode to use this for my Automations in KNX.
Therefore it is necessary to add following sensor which is not yet available in PyViCare:
heating.circuits.N.operating.modes.cooling

Activity

  1. lackas commented on Jul 7, 2026

    @lackas
    Collaborator

    Hi @bekra00,

    a summary of what we found while digging into this.

    heating.circuits.N.operating.modes.cooling turned out to be a mode-selection/config flag, not a runtime state. On our own Vitocal 300-G (CU401B) I watched natural cooling run live (the buffer dropped from 42 to 19 °C) while heating.circuits.1.operating.modes.cooling stayed active: false, and the selected mode was the umbrella dhwAndHeatingCooling, so getActiveMode() never returns cooling.

    Unfortunately, on our setup there is no clean "cooling is running now" flag in the API. Because it is natural cooling (no compressor), the compressor metrics stay 0 as well: getCoefficientOfPerformanceCooling() = 0 and power.consumption.cooling = 0. The only way we could tell cooling was active was the temperature signature, the circuit supply / system return / buffer dropping well below heating level (secondary supply went from ~42 °C to ~16 °C). Those thresholds are specific to each installation, so they do not generalize into a reliable getter, which is a pity.

    For active cooling (compressor reversal, e.g. Vitocal 250-A) it should be easier: getCoefficientOfPerformanceCooling() > 0 or CoolingCircuit.getReverseActive() should indicate it.

    To see whether a general indicator exists, could you (and anyone else here) help with a bit of data:

    • Which device model, and active or natural cooling?
    • A diagnostics dump (or the raw feature list) once with cooling clearly running and once without, so we can diff which feature actually flips.
    • If you spot any feature on your device that reads true or nonzero only while cooling, please paste it here.

    With a few examples across setups we can tell whether there is a common signal worth exposing, instead of a per-installation temperature heuristic.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

      Milestone

      No milestone

      Relationships

      None yet

      Development

      No branches or pull requests

      Issue actions